SIMPLEX 4004R SUPPRESSION RELEASE PANEL

The Simplex 4004R is a two-hazard releasing system that incorporates big-panel features into a small and cost-effective package. Its dual hazards can be programmed to provide an agent release for one hazard and preaction or deluge for the other, giving a high degree of flexibility and protection.  With the early detection capability of the agent release hazard, the fire should be extinguished before the preaction or deluge system is activated.
Highlights:

Fire alarm control panel designed specifically for suppression release operation –   4004R panel is purpose built suppression release panel whose features include:


    • Four initiating device circuits (IDCs)
    • Two notification appliance circuits (NACs)
    • Two releasing appliance circuits (RACs)
    • Two special purpose monitor inputs (SPMs) that accept manual release request and manual abort request for Agent Release systems, and waterflow and supervisory for Preaction or Deluge systems
    • Three auxiliary relays with selectable functions

 

Suppression release operation – Supported release modes include:


    • Automatic extinguishing release
    • Deluge and preaction sprinkler system release
    • Dual or single hazard area protection
    • Combined agent release and preaction operation

 

Audible Escalation of Events –  Stage 1 activates Temporal or 20 bpm March Time pattern; Stage 2 activates 120 bpm March Time pattern to indicate release timer active; Release activates On Steady to indicate release timer expired and actuator is activated.

Event Log – A 50-point historical log allows you to investigate the cause of a release after the event.
 
Flexible Programming – The 4004R can be programmed from the ront panel or from a PC.